Service

Precautions

  • Use Proper insulated tools during installation / service

  • The Lifting equipment of the batteries must withstand to hold the module weight during installation

  • Always follow the O & M Manual safety instructions

  • Avoid installation damages

  • Avoid short circuits


Space Consideration

  • Install VRLA battery bank in a clean, cool and dry location

  • VRLA Battery bank installation floor should be reasonably levelled

  • The location having an ambient temperature of 24° C to 30° C will result in optimum VRLA battery life and performance


Floor Loading

  • The Amaron Quanta VRLA batteries weight has been given in the Opera & Maiu manual.

  • The total System weight can be calculated from the Opera & Maiu Manual If floor loading exceeds the permissible limits, assemble the VRLA batteries on separate rack or approach ARBL nearest office for suggestions


Ventilation

  • No separate ventilation or battery room is required for VRLA batteries

  • Normal room ventilation is sufficient


Floor Anchoring

  • Generally the system does not required to be anchored

  • Where seismic conditions are anticipated, floor anchoring, should be provided

  • Such anchoring is the responsibility of the customer/end user


Temperature Variations

  • Sources of heat or cooling directed to a portion of the battery bank can cause temperature variations within the system

  • Results in module voltage differences and lead to premature failure of VRLA Battery system


Tools

  • 3.5 Digit Multimeter with RMS value (Ripple) measurement

  • Spanner set


Safety

  • In normal use, Amaron Quanta VRLA Batteries will not generate or release hydrogen, oxygen gases, or acid mist and will not have acid leak. They are inherently safer than conventional lead acid batteries

  • However, there is a possibility that under abnormal operating conditions or as a result of damage, misuse and/or abuse, these potentially hazardous conditions (gassing, acid mist, and leaking electrolyte) can occur

  • Thus Amara Raja recommends that the instructions entitled "SAFETY PRECAUTIONS" be reviewed thoroughly and strictly followed when working with Amaron Quanta VRLA Batteries.

 
 
©
Back to content | Back to main menu