Charging Instructions - Amithi_Energy

Today:
Go to content

Main menu:

Charging Instructions

Service

Constant voltage current limiting charging method is most suitable for Amaron Quanta - MVRLA batteries

Float Mode                         :   13.50Volts
Boost Mode                          :   13.80Volts
Current Limit                      :   25% of rated Ah
Ripple allowable                :   < 2% rms
O/P Voltage regulation       :   ±1%
Over Voltage cut off            :   14.00Volts
Under Voltage Trip              :   10.50Volts

 
©
Back to content | Back to main menu